Facade Wind Loading

Today, most of the buildings have curtain walls. This increases the importance of using glass / composite materials. Calculation of the wind load on the façade by regulations varying between countries due to structure height, form and surrounding structures has been excluded from analytical calculations. The most widely used standard for Turkey “TS 498” not high structures (building height, which is made of less than 30.5m) with a fairly quick calculation is enough to get a solution. Internationally, the most widely used document in our region is “Eurocode EN 1991-1-4: Actions on structures, Part 1-4: Wind actions”. Every country maintains equivalent standards and regulations.

Alkazar’s practical calculation module for EN 1991-1-4, the Facade Wind Load Calculation Module, is part of UrClimate Tailor and is available to subscribers here:

Facade Wind Loading

Facade Wind Load – Tunnel Test & CFD Services

Worked example: basic dynamic pressure

The first step of the analytical approach is the dynamic pressure formula: q = 0.5 × ρ × V². If we assume the wind velocity at a given height as V = 10 m/s and the density of air as ρ = 1.225 kg/m³ (standard air density at sea level):

StepCalculationResult
Dynamic pressure0.5 × 1.225 × 10²61.25 N/m² (Pa)
kgf/m² equivalent61.25 / 9.80665≈ 6.2 kgf/m²

This is the reference dynamic pressure on the façade, before any zonal pressure coefficients are applied. In TS EN 1991-1-4, once the façade is divided into zones A–E, this reference value is multiplied by each zone’s own coefficient; in practice it is not the average value but the higher suction at corners and edges that governs. On a real project, V is derived from the site’s basic wind speed, terrain category and height-dependent corrections; the 10 m/s used here is simply an illustrative input to show the calculation step. Completing this process with purely analytical approaches requires knowing the varying wind speed for each region under many conditions, which is why our wind profile calculator and WindCalc module automate these steps.

Facade Wind Loading

Critical situation in which the standards are not sufficient in calculating facade loads; It is problematic that the wind speed varies depending on the altitude and it cannot be predicted at what height the wind will blow due to the buildings and surrounding buildings where the calculations are made.

Therefore, the points to be considered in the analysis studies;

  • Topography details,
  • Surrounding structures,
  • Surface roughness of the land.

Atmospheric Boundary Layer Wind Profile is defined to the boundary conditions by maintaining the entire flow volume. When the wind profile is created for analysis, the structure is exposed to wind load with angle changes of 10 with the automation developed by Alkazar. Thus, the load (positive) and suction (negative) load values that occur in 36 different directions in the facade surface are calculated. Subsequently, these loads are reported to the employer in 3D format and delivered to the building.

Facade Wind Loading

Reporting of 36 different direction wind load values in a single (3D format, .dwg, .dxf, .3dm) file

Thanks to computational calculation of wind load, it provides cost advantage by getting rid of the values that may be high tolerance value on the investor front. Or it can detect overloads at unpredictable points. The application firm or project managers will be presented in detail in which region the load will be critical. Thus, a report is prepared for the direct use of the facade consultants, the teams performing the calculations of the façade statics or the application side. In the delivered reports, a separate load value is calculated for each cladding zone and this detail cannot be used during the application. However, it is important to know all the risks in practice and make decisions accordingly. In this way, detailed reports increase the practice of our employers.

In determining the static loads that will affect the building core and defining the acceleration levels that will occur under wind load, we are at your side with a CFD set-up aligned with boundary-layer wind tunnel practice. Alkazar does not operate a physical wind tunnel; this is why it is important that the set-up provides the necessary and sufficient conditions for the atmospheric boundary layer.

TS 498 ↔ TS EN 1991-1-4 ↔ CFD comparison

TS 498TS EN 1991-1-4CFD simulation (Alkazar)
ScopeFixed suction/pressure values by height; fast and simpleDetailed calculation with terrain category, turbulence, topography and zone coefficientsNumerical solution of the flow field for the actual geometry and surrounding context
Height limitFast solution for non-high-rise buildings under 30.5 mApplies across the full height range, including tall buildingsNo height limit; preferred for tall or irregular buildings
Surrounding effectDoes not cover neighbouring-building effects, funnelling or re-entrant cornersGeneral rules; numerical analysis/wind tunnel recommended for complex surroundingsSheltering/channelling from neighbouring buildings is modelled directly
OutputA single pressure/suction value varying with heightZones A–E and coefficients depending on loaded areaPressure coefficients and cladding-zone maps for every 10° of wind direction, plus 3D result files

Process and deliverables

StepsDeliverables
Definition of the wind profile → CFD simulation (in 10° angle increments, 36 directions) → calculation of pressure/suction → cross-check against TS 498 / TS EN 1991-1-4Positive (pushing) and negative (suction) pressure values for 36 directions; cladding zone maps; 3D results in a single file (.dwg, .dxf, .3dm)

What does the Istanbul High-Rise Wind Regulation require?

Short answer: Under the Istanbul High-Rise Wind Regulation (Istanbul Tall Buildings Wind Code, Version V), the wind effects of every high-rise design within its scope are to be approved by an independent control board. For non-standard structures the regulation requires a physical wind tunnel test. CFD makes the code calculation site-specific and shows local peak pressures across the facade zones.

Source: Istanbul High-Rise Wind Regulation (Istanbul Tall Buildings Wind Code), Version V (Boğaziçi University Kandilli Observatory, for the Metropolitan Municipality, August 2009). Whether the authority refers to this text should be confirmed for each project.

Example workflow: a hypothetical 120 m office tower

StepCode and standard calculationCFD study
Wind inputBasic wind speed, surface roughness and topography factors from the regulationAn atmospheric boundary layer profile defined with the same inputs; a separate solution for each wind direction
SurroundingsGeneric assumptions; the effect of neighbouring buildings is only partly coveredThe surrounding built context is modelled, so acceleration and sheltering are resolved directly
Facade pressurePressure coefficients for corner, edge and field zonesPeak and area-averaged pressure coefficients across the cladding zones
ResultEnvelope values that cover a wide family of buildingsSite-specific values; the reason for any difference from the code calculation is explained in the report

This table is a hypothetical workflow showing how the methods complement each other; it contains no numerical result. For a first estimate see the facade wind load calculator; the steps of the calculation are in our wind load calculation guide (tables, Eurocode, regulation).

Let us discuss your project

A short first call to agree scope, timeline and deliverables. The same team that does the work answers.

Write to us by email Request a call

Reference projects

Facade wind loading: code calculation, CFD or wind tunnel?

Short answer: Alkazar calculates facade wind loads with CFD simulation, cross-checked against EN 1991-1-4 (Eurocode 1-4) and TS 498, for every 10° of wind direction. Deliverables are pressure coefficients, cladding zone maps and 3D result files. See also wind & CFD consultancy and pedestrian-level wind comfort.

Frequently asked questions

What is facade wind loading analysis?
It is the calculation of the peak positive (pushing) and negative (suction) pressures the wind applies to the building envelope, so that glass, panels, fixings and the supporting structure can be specified safely. Results are reported as pressure coefficients and cladding zones; corners, edges and parapets typically govern.
When is CFD required instead of the Eurocode calculation?
When the building is tall or irregular, when neighbouring buildings shield or channel the flow, when there are podiums, setbacks, canopies or double-skin facades, or when the code’s generic assumptions would be too conservative or unsafe for the actual geometry.
Why can the Eurocode give higher loads than a simulation?
Code values are envelope values, calibrated to cover a wide family of buildings and surroundings with a safety margin. A simulation reproduces the actual geometry and context, so local pressures often come out lower, and in some sheltered or channelled configurations, higher. We compare both.
What is delivered?
Pressure results for each wind direction (typically every 10°), cladding zone maps, peak and area-averaged coefficients, and 3D result files in the file formats the facade consultant or structural engineer requests.
What determines the price of a facade wind loading study?
It depends on the building’s height and geometry, the density of the surrounding urban context, the number of wind directions analysed, and the requested output formats; the final price is set according to project scope.
Is CFD useful on a project where a wind tunnel report is required?
Yes. Alkazar’s CFD set-up is aligned with boundary-layer wind tunnel practice: an atmospheric boundary layer inflow profile, modelling of the surrounding built context, and directional analysis in 10° increments; so results can be read alongside wind tunnel reports and code-based calculations. Alkazar does not operate a physical wind tunnel.
Which buildings does the Istanbul High-Rise Wind Regulation cover?
All high-rise designs that fall within its scope. The scope and thresholds are defined in the regulation text; we recommend confirming at the start of the project, from the text and with the relevant authority, whether your project is covered.
Does CFD replace a wind tunnel test?
Not always. If the regulation or the specification asks for a physical test, CFD does not take its place. On projects with no such requirement, CFD guides the facade design early, makes local peak pressures visible and explains the difference from the code calculation. Which one is needed depends on the regulation, the specification and the authority’s request.
Should I commission a wind tunnel test or CFD for my facade?
A tunnel test is needed if the regulation, specification or authority asks for it. If not, and the aim is to assess facade zone pressures, the effect of surrounding buildings and design alternatives early, CFD is suitable. The two can also be used together. Let us define the right method for your project together. For a detailed comparison, see our guide Wind tunnel or CFD?
Does Alkazar perform wind tunnel tests?
No. Alkazar does not operate a physical wind tunnel and does not perform tunnel tests; it calculates facade wind loads with CFD simulation. We can help you assess, from the regulation and specification, whether a tunnel test is needed on your project.

Related calculator: Alkazar WindCalc is an engineering module that calculates façade zones (A–E) and pressure coefficients for rectangular, L-, U- and T-shaped plans using the TS EN 1991-1-4 approach; it is available with an UrClimate Tailor subscription. For a quick pre-check, try our U-value calculation tool and wind profile calculator (Turkish-language tools). The calculation steps, the TS 498 height table and the codes used in Türkiye are explained in our wind load calculation guide.

Related article: Rooftop solar panel: Position and orientation change the wind effect together

Download Facade Wind Loading Form

Solutions

Teklif Alın

Get a quote

Alkazar Technology
Privacy overview

No cookie other than the strictly necessary ones is placed on your device before you opt in. You can switch each category on or off separately and change your choice or withdraw your consent at any time through the "Cookie settings" icon in the corner of the page. Controller: Alkazar Mühendislik ve Danışmanlık Ltd. Şti.