Most data centres in the Gulf are designed against a published design temperature. That number describes an airport weather station. The project is rarely at the airport. And the climate that produced the number keeps moving. We have prepared three sample Site Design Conditions cards for Dubai, Riyadh and Doha to show what changes when you look at the station, then the site, then the horizon.

What the three cards show

Page 1 of each card is a design conditions table in the familiar station-page layout. We computed it from 30 years of hourly station observations, 1996 to 2025, following the ASHRAE Handbook Fundamentals Chapter 14 method. These are Alkazar computed values, not ASHRAE published values. Below the table, a “Station to Site” block adds an estimate for a site point away from the airport.

CityStation0.4 % cooling DB at the station20-year return extreme DBHours per year at or above 45 °C, station0.4 % DB at the site point (estimate)
DubaiDubai International (WMO 41194)43.8 °C47.8 °C1344.5 to 45.5 °C (Dubai Production City area, 31 km from the station)
RiyadhRiyadh King Khalid International (WMO 40437)45.0 °C47.9 °C5445.2 °C
DohaDoha International (WMO 41170)45.0 °C49.1 °C3745.3 °C

Table note: computed by Alkazar from hourly station observations, 1996 to 2025, following the ASHRAE Handbook Fundamentals Chapter 14 method. Not ASHRAE published values. The 0.4 % cooling dry-bulb is exceeded for about 35 hours in an average year. The 20-year return extreme is the single peak expected once in 20 years. Site estimates use the Copernicus ERA5-Land offset between station and site point and are labelled as estimates on the cards.

From the station to the site

The station is the only place where a thermometer actually sat for 30 years. We keep it as the anchor. To move to the site we take the Copernicus ERA5-Land difference between the station grid point and the site grid point over the same 30 years, and add it to the observed station value.

Why not read the reanalysis directly at the site? Because it smooths the extremes. At Doha, reanalysis alone gives 42.3 °C at the station for the 0.4 % level; the station observed 45.0 °C. A 2.7 °C gap on the design day is not a rounding error. Reanalysis is good at the difference between two nearby points, not at the absolute value on the hottest afternoons. The station gives the level, the reanalysis gives the offset, the site gets both.

Dubai shows why the step matters. The site point is in the Dubai Production City area, 31 km from the airport. The estimate there is 44.5 to 45.5 °C against 43.8 °C on the station page. At 31 km we give a band, not a point.

What it means for the plant yard

Page 2 of each card walks through three pieces of equipment.

Chillers. The condenser side is selected at the design ambient. Capacity and power follow the manufacturer’s curve as the ambient rises. The card does not change that curve. It tells you which point on it to read.

Dry coolers. A dry cooler can only bring the water down to ambient plus its approach. At 45 °C the margin to what chillers and plant accept is thin. The hours at or above 45 °C in the table are where that margin is tested: Riyadh 54 a year at the station, Doha 37, Dubai 13.

Generator yards. Engines and alternators derate with inlet air temperature. Radiator inlet air in a yard sits above ambient when the discharge from one set finds its way into the next. The card gives the ambient at the site, not the recirculation. That number comes from an external airflow study of the yard at the site design conditions, our second offer below.

The horizon is the third step. The cards describe 1996 to 2025. A version at future warming levels is available on request. It is not in this print run.

Get the three cards, or one for your own site

The three detailed cards (Dubai, Riyadh, Doha) are free to download. Fill in the short form and the links arrive by e-mail.

If your project is not at an airport, we offer two services:

  • O1. Site Design Conditions Card for your own coordinates. Same method, same layout, your site. Five working days. Fixed price on request.
  • O2. Plant Yard and Exhaust Check. External airflow CFD of the cooling yard and generator exhaust at the site design conditions. Three weeks. Fixed price on request.

Download the Gulf design conditions cards

Which cards

Teklif Alın

Get a quote

Alkazar Technology
Privacy overview

No cookie other than the strictly necessary ones is placed on your device before you opt in. You can switch each category on or off separately and change your choice or withdraw your consent at any time through the "Cookie settings" icon in the corner of the page. Controller: Alkazar Mühendislik ve Danışmanlık Ltd. Şti.